HomeMy WebLinkAbout0368_001lepartrrient ,ntorcement TO: BE ARCHITECTS , FROM: LYLE DOERR, BUILDING O.FFICIAI RE: PLAN REVIEW OF IMMUNO NUCIJF,AR BUILDING AT 1951 NORTHWESTERN AVE., STILLWATER DATE: DECFTMF,R 18, 1980 In making the plan rev.iow of the structure by our staff and the Stillwater Fire Chief', these items wore rioted. 1) The type of cons trLiction is 21-N. 2) The occupancy IN p--2. 3) 'rhe maximum occupancy .load of the str-iictu.re was determined to be 180. 14 ) A1.1 plumbing must be installed for Minnosota Plumbing Code (MILD 120- 135.) Laboratory sinks in equipment (107) and research (105) rooms must. be equipped to handle special wart, es (MILD 1,'9d. ). 5) Ventilation, heating and air-conditioning must be installed per SBC 7101. Laboratory benches in equipment (107) and research (105) rooms must have a separate exhaust system (SBC 7711). Mechanical calculations must be submitted .for approval prior to installing any equipment. 6) Building must be accessible to handicapped. (Chapter 55 of the State Building Code) This would require both stairs to have closed risers (2 MCAR - 1.15502 - G). 7)" Sprinkler plan must be submitted for approval. 8) Flammable liquids may be stored in storage area (Room 209) per Chapter 9 of UBC and Fire Code section 15.403. No individual container shall exceed five gallons and not over 120 gallons shall be stored in any one approved cabinet. Of this total, not more than sixty gallons may be of Class I and Class II liquids. When approved by the Fire Chief, three approved cabinets may be located in an area. Also, materials being stored must be kept at least 36 inches below sprinkler deflectors (Fire Code 35.105-h). 14900 61st street north stillwater, minnesota 55082 (612) 435-3220 Be Architects December 18, 1980 Page Two 9) Radioactive material may require permit frOM the United States Atomic Energy Commission (Fire Code; 19.102) . Radioactive mate- rial to be identified and stored per Fire Code (Secti0rr, 19.105). 10) Office partitions and equipment must be placed in accordance with Section 3313 of UBC. Partitions cannot be used to form exit corridors. LCD/mms